Spatial Specifications

Building-science metrics for the physical plant

This companion brief translates each Socratic learning goal into measurable criteria for architects, contractors, school-board developers, and facilities staff. The numbers are targets, not ornaments: they protect the conditions that let attention, dialogue, and neuroplasticity flourish.

How to use this document

From intention to measurable criteria

Every row pairs a design intention with a target metric. Some targets are drawn from established building-science standards; others are specific to the Academy's method. Use the table as a baseline for design review, contractor bidding, and post-occupancy evaluation.

Where a target conflicts with budget or code, document the deviation and its expected impact on learning. The building is a teacher; compromises should be made knowingly.

Cost note. These specifications describe a high-performance learning environment. Delivering them in a new-build campus — land, structure, MEP, building-technology integration, and landscape — is a several-million-dollar capital project separate from the $662,900 pilot operating budget. Donated hardware or software can reduce the visible technology line, but the expert time to meet these targets — architects, acousticians, MEP engineers, landscape designers, and systems integrators — would cost many multiples of the pilot's $73,400 technology allocation. Treat the specs as the target brief for that capital phase, not as a price list for the pilot year.

Daylight and visual environment

MetricTarget
Useful daylight illuminance (UDI)300–3,000 lux for >50% of occupied hours
Glazing ratio≥40% of floor area on two orientations where possible
View qualityDirect line of sight to vegetation from every occupied position
Artificial lightingFlicker-free, dimmable, CRI ≥90, tunable-white to match circadian phase
Color temperature4,000–5,000 K during active hours; warmer in evening programs

Acoustics

MetricTarget
Background noise level (NC)NC-25 to NC-30 in learning zones
Reverberation time T600.4–0.6 s for Socratic circles; up to 1.0 s in music salon
Wall geometryNon-parallel primary surfaces with ≥15° deviation from parallel
Acoustic absorptionNRC ≥0.75 on ≥30% of ceiling and upper-wall surface
Sound transmission class (STC)STC ≥50 between learning rooms and active zones

Materials and indoor air quality

MetricTarget
VOC emissionsCDPH Section 01350 compliant; formaldehyde < 9 µg/m³
Allergen controlNo latex, no added fragrance, low-protein animal fibers only
Primary finishesSolid timber, clay plaster, natural cork, untreated wool, stone
Surface touchWarm-to-touch natural materials on surfaces below 1.2 m height
Moisture managementVapor-open assemblies; relative humidity maintained 40–60%

Compute and AI stations

MetricTarget
Station densityOne station per 8–10 students; perimeter placement only
Display≥24 in, anti-glare, adjustable arm, blue-light reduction after 14:00
NetworkWired gigabit to each station; redundant wireless coverage
AudioDirectional microphone + noise-canceling headphones for oral Socratic sessions
ErgonomicsSit-stand desk surface; chair sized to student anthropometrics

Gathering and sprawl spaces

MetricTarget
Gathering table sizeSeats 10–14; clear sightlines; central location per room
Sprawl floor area≥25% of learning-room area with varied cushion heights
Floor finishResilient natural-fiber surface; easy to clean; non-slip
FlexibilityMovable furniture on casters or lightweight enough for students to reconfigure
Social densityNo long rows; clusters of 4–6 to support peer dialogue

Music, dance, and movement

MetricTarget
Music salon area≥20 m² with instrument storage and acoustic separation
Instrument inventoryPercussion, counting-blocks, simple stringed instruments, all within child reach
Dance floorSprung wood or equivalent resilient surface; clear ceiling height ≥3.5 m
MirrorsOptional, partial, and removable to avoid over-emphasis on appearance
VentilationDedicated outdoor air rate 1.5× standard classroom minimum

Outdoor connection and biophilia

MetricTarget
Outdoor learning areaCovered porch or pavilion adjacent to each learning room
Nature accessEvery room within 30 m of planted ground or garden
Native planting≥70% native species; no neonicotinoid-treated plants
Walking pathsLooped trail ≥200 m total on or adjacent to campus
Water featureSmall recirculating feature or rain garden for sensory calm

Ventilation and thermal comfort

MetricTarget
Outdoor air rate≥10 L/s per person; demand-controlled CO₂ < 800 ppm
Temperature20–24 °C during occupied hours; radiant asymmetry < 5 °C
Air filtrationMERV-13 minimum; portable HEPA units in high-activity zones
Operable windowsWhere climate allows; interlocked with mechanical systems
Thermal zoningPer-room control; no hot/cold spots at student level

Verification

Commissioning and post-occupancy review

The campus should be commissioned against these metrics before students arrive. After occupancy, repeat key measurements annually: daylight levels, acoustic reverberation, CO₂, and temperature uniformity. Student and guide feedback is also a metric — if the space feels hurried, loud, or sterile, the numbers are not yet right.